IS2000 - Facility Code not provided in Event Manager

If you get a Bit Number but do not get a Facility Code in the Event Manager, then double-check that the data and clock wires (White & Green) have been landed on the proper termininals.  Having the wire in the reverse will cause this type of display and correcting the termination will provide the FAC Code on the next card swipe.   Reader White wire goes on Clock (D1 +) and Green wire goes on Data (D0 -) terminals.