Mercury Triggers and Macros- Airport Doors

Drive Gate Settings

Input Supervision for input 1: 0 normally closed 
Input Supervision for input 2: 1 normally open 
Note: If input 1 and/or input 2 are red, in the hardware properties, then check wiring
Default reader mode: Card Only (for both readers) 
Door Held Time, Door Contact Input 2: 50 seconds 
Output 1 Pulse Time: 35 seconds 
Reader 1, Reader settings: 001-Paired (Master) 
Reader 2, Reader settings: 002-Paired (Slave) 

Door Definitions:

Door Strike: 0: door has no impact on strike control
For Reader 1, select Paired (Slave) Reader: the second reader
For Reader 2, select Paired (Master) Reader: the first reader
Door Contact Address: Input 2
REX1 Address: Input 3
REX2 Address: None

 

Crash Bar Door Type:

Door Strike Pulse Time = 5 seconds
Door Held Open Time = 16 seconds
Input #2 is a Monitor Point, no REX configuration

Baggage 30 Door Type:

Door Strike Pulse Time = 10 seconds
Door Held Open Time = 1800 seconds (30 minutes)
Door Strike Mode = No Impact
Only cards with Trigger Code 1 will work


Baggage 60 Door Type:

Door Strike Pulse Time = 10 seconds
Door Held Open Time = 3600 seconds (60 minutes)
Door Strike Mode = No Impact
Only cards with Trigger Code 1 will work
Drive Gate Door Type:
Door Strike Pulse Time = 45 seconds
Door Held Open Time = 60 seconds
Door Strike Mode = No Impact
Only cards with Trigger Code 1 will work
Input #2 is a Monitor Point, no REX configuration


Jetway Door Type:

Door Strike Pulse Time = 5 seconds
Output #2 Pulse Time = 5 seconds
Door Held Open Time = 1800 seconds (30 minutes)
Door Strike Mode = No Impact
Only cards with Trigger Code 1 will work