Mercury EPC/SCP

Mercury EPC/SCP

To access the network page of the SCP-2 Mercury controller, follow these steps: Power the Mercury controller down Flip all dip switches to the ON position and re-apply power to the controller From a browser type http://192.168.0.251 Enter the User Name:  admin Enter the Password:  password Note:  In order for…
• EPC-1/SCP-2 controllers are defaulted out of the factory as 192.168.0.251, with all four dip-switches on. • Perform a direct connect to the controller via cross-over cable and a PC/Laptop with IP address of 192.168.0.250.   • Launch the browser and enter the controller address 192.168.0.251.   • To login,…
Supporting 250,000 Cardholders per Controller In order to allocate enough RAM in the SCP-2, SCP-M, and/or EPC-1, you MUST first disable some of the features that take up most of the RAM.  One in particular is the number of access levels that a card holder can have per record. Copy…
The Mercury driver logs the date/time stamp according to the PC's Time Zone configuration.  You can change the PC's Time Zone setting via the operating system, or you can set the Zulu_Time property to 1 in the RemotePath\Drivers\12000.ini file under the [General] section.  Please note that it is recommended that…
An input point is a physical object located on a sub-controller that measures the resistive value of a circuit connected to it.  This resistive value is translated to a numeric value that the SCP/EPC can interpret.  Not only can inactive and active states be sensed, but also particular types of…
MEMORY ALLOCATION for SCP Compact & Expanded boards A)  Precision Access set to TRUE # Of Cards                   % of free memory Allocated                   on the Controller SCP-C         1000----------------------------------34%     …
For nearly 20 years Mercury Security has steadfastly practiced the singular art of building access control hardware.   Since 1992 in collaboration with OEM partners like IMRON Corporation, we have built an unmatched set of features into an Open hardware platform that is unequaled for reliability, longevity and effectiveness…
Add the following properties and values to the RemotePath\Drivers\12000.ini file under the section [Controller_1.0] where 1.0 represents the controller's address.  Please note that you will need to make sure that properties and values listed below must be in each controller's section.: ;enable the dual port features for this controller (0=disabled …
Description
Mercury
IMRON
Lenel
RS2
Open Options
Maxxess
*Controller- C for compact, 512KB on Board SCP-C SCP-C LNL-500 Mini-SCP SSP-C NA
*Controller- Gateway for Wireless Schlage Readers SCP-C SCP-C LNL-500W Mini-SCP SSP-C NA
*Controller- S for Standard, 3MB Memory board (Total 4MB) SCP-S SCP-S LNL-1000 SCP SSP NA
*Controller- E for Expand up to 8MB (1MB on Board) SCP-E SCP-E LNL-2000 SCP-E SSP-E NA
Controller- Single door (6MB on Board) EP-1501 EPC-1 LNL-2210 EP-1501 NA eMax-EP1501
Controller- 2 on-board reader ports (6MB on Board) EP-1502 SCP-2 LNL-2220 EP-1502 SSP-D2 eMax-EP1502
Controller- M for Mega, (15MB on Board) EP-2500 SCP-M LNL-3300 EP-2500 SSP-EP eMax-EP2500
Sub-controller- Dual reader support MR-52 MR-52 LNL-1320 MR-52 RSC-2 eMax-MR-52
Sub-controller- Single reader support MR-50 MR-50 LNL-1300 MR-50 RSC-1 eMax-MR-50
Sub-controller- 16 Inputs MR-16IN SI-16 LNL-1100 MR-16IN ISC-16 eMax-MR16IN
Sub-controller- 16 Outputs MR-16OUT SO-16 LNL-1200 MR-16OUT OSC-16 eMax-MR16OUT
Multiplexer- Provides 8 RS-485 comm buses MUX-8 MUX-8 LNL-8000 MUX-8 MUX-8 NA
Multiplexer- Provides 4 RS-485 comm buses MUX-4 MUX-4 LNL-4000 MUX-4 MUX-4 NA
  * These items are no longer available from Mercury as of Jan 2009.  
The firmware download should be done 1 controller at a time.  Once the firmware is loaded the version will display in the controller status screen as x.xx. After which perform a reset to sync the host database with the controller. Please note that firmware downloads can take up to 5…