Sku: H-V100

VertX V100 Two Door Sub-Controller

 Data Sheet

Overview

The V100 Door/Reader interface connects two access control card readers via Wiegand or Clock-and-Data interface controlling either one or two doors. The V100 features on-board flash memory, allowing program updates to be downloaded via the network. The V100 connects to the V1000 through a high speed RS-485 network. The V1000, in turn, communicates with the system host via industry standard TCP/IP protocol over 10/100 Mbps Ethernet or the Internet. This architecture minimizes the impact on corporate LANs by using only one TCP/IP address for every 32 interfaces and by handling low-level transactions on the RS-485 network.

 

VertX V100 2 Door Sub-Controller

  • 2 Reader Ports
  • 2 REX Inputs
  • 2 Door Contact Inputs
  • 2 Lock Dry Closure Relays
  • 2 Aux Relays
  • Tamper Input, AC & Battery Fail Inputs

 

Key Features

  • Reports supervised inputs.
  • Connects to the V1000 via RS-485.
  • Receives and processes real time commands from the V1000.
  • Reports all activity to the V1000.
  • Attractive polycarbonate enclosure protects components from damage.
  • All connections and indicators are fully identified by silk-screened nomenclature on the cover.
  • Processes off-line access control decisions based on facility code.
  • UL 294 and UL 1076 recognized components.

 

Dimensions

5.8' W x 4.825' H x 1.275' D (147.32 mm x 122.55 mm x 32.38 mm)

 

Weight

12.4 oz (.35 kg)

 

Power Supply Requirements

60 mA @ 9-18 VDC (with no readers connected) Recommended: Supervised linear power supply with battery backup, input surge protection, and AC fail and battery low contact outputs. When VertX is supplying power to readers the requirements are 600 mA @ 9-18

VDC. The V100 can supply 500 mA to two readers.

 

Cable Distance

RS485 – 4000 feet (1220 m) to host, using Belden 3105A, 22AWG twisted pair, shielded 100Ω cable Wiegand – 500 feet (150 m) to reader – using ALPHA 1299C 22AWG, 9-conductor, stranded, overall shield (Fewer conductors needed if all control lines are not used).

Input Circuits – 500 feet (150 m), 2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C (18AWG) 

Output Circuits – 500 feet (150 m), 2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG)

Minimum wire gauge depends on cable length and current requirements.

 

Operating Environment

Indoors, or customer-supplied NEMA-4 rated enclosure

 

Temperature

32° to 122°F (0° to 50°C)

 

Humidity

5% to 95% relative, non-condensing

 

Communications Ports

RS-485 – two wire. Two SIA standard Wiegand/Clock-and-Data ports

 

Certifications

UL 294 and UL 1076 Recognized Component for the US

CSA 205 for Canada

FCC Class A Verification

EMC for Canada, EU (CE Mark), Australia (C-Tick Mark),

New Zealand, Japan

EN 50130-4 Access Control Systems Immunity for the

EU (CE Mark)